Quesco CC Print
PDF
Part Number
Cross Section
Rated Voltage
Maximum Temperature of the Conductor During Operation
Maximum Temperature of the Conductor During Short circuit
Max. Tensile Load During Installation and operation
Minimum Overal Diameter
Maximum Overal Diameter
Nominal Cable Weight










mm2
Uo/u
0C
0C
N
mm2
mm
Kg/m
FEC325
3X35+3X10
3.6/6kV
90
250
1500
37.5
40.5
2.400
FEC335
3X35+3X10
3.6/6kV
90
250
2100
40.3
43.3
2.900
FE0350
3X50+3X10
3.6/6kV
90
250
3000
44.7
47.7
3.600
FEC370
3X70+3X16
3.6/6kV
90
250
4200
49.5
52.5
4.670
FEC395
3X95+3X16
3.6/6kV
90
250
5700
54.0
57.0
5.800
FEC30A
3X120+3X25
3.6/6kV
90
250
7200
57.5
60.5
7.000
FEC30B
3X150+3X25
3.6/6kV
90
250
9000
62.0
66.0
7.800
FEC30C
3X185+3X25
3.6/6kV
90
250
11100
66.0
70.0
9.700
FED325
3X25+3X10
6/10kV
90
250
1500
41.0
44.0
2.800
FED335
3X35+3X10
6/10kV
90
250
2100
44.0
47.0
3.300
FED350
3X50+3X10
6/10kV
90
250
3000
48.0
51.0
3.950
FED370
3X70+3X16
6/10kV
90
250
4200
53.0
56.0
5.000
FED395
3X95+3X16
6/10kV
90
250
5700
57.0
61.0
6.000
FED30A
3X120+3X25
6/10kV
90
250
7200
61.5
65.5
7.300
FED30B
3X150+3X25
6/10kV
90
250
9006
66.0
70.0
8.650
FED30C
3X185+3X35
6/10kV
90
250
11100
70.0
74.0
10.000
FEE325
3X25+3X10
8.7/15kV
90
250
1500
45.0
48.0
3.100
FEE335
3X35+3X10
8.7/15kV
90
250
2100
48.0
51.0
3.750
FEE350
3X50+3X10
8.7/15kV
90
250
3000
52.5
55.5
4.450
FEE370
3X70+3X16
8.7/15kV
90
250
4200
57.0
61.0
5.600
FEE395
3X95+3X16
8.7/15kV
90
250
5700
62.0
66.0
6.800
FEE30A
3X120+3X25
8.7/15kV
90
250
7200
67.0
71.0
8.000
FEF325
3X25+3X10
12/20kV
90
250
1500
52.0
55.0
3.700
FEF335
3X35+3X10
12/20kV
90
250
2100
53.7
56.7
4.200
FEF350
3X50+3X10
12/20kV
90
250
3000
56.2
60.2
4.880
FEF370
3X70+3X16
12/20kV
90
250
4200
61.0
65.0
6.000
FEF395
3X95+3X16
12/20kV
90
250
5700
67.0
71.0
7.300
FEF30A
3X120+3X25
12/20kV
90
250
7200
70.0
74.0
9.000
Medium Voltage Power cable - Rubber insulation Special Extruded Screen
Reduced weight and dimension
14. MEDIUM VOLTAGE POWER CABLES ® (N)
TSCGEWOU VDE 0250 p. 813 (as applicable) & HD 620 s1 I
TRATOSFLEX® - ES (Extruded Screen) -
Reduced weight and dimension NEW - REDUCED HALOGEN (if required)

FEATURES AND PERFORMANCES

Rated Voltage 3,6/6 kV 6/10 kV 8,7/15 kV 12/20 kV
Max Voltage AC 7,2 kV 12 kV 18 kV 24 kV
AC Voltage Test 11 kV 17 kV 24 kV 32 kV
1- Conductor more flexible than CI. 5 VIDE 0295
2- Semiconducting layer + HEPR insulation + semiconducting layer*`
3-Ground conductor with semiconducting layer
4- Inner Sheath
5- antitorsional protection
6-Outer sheath 5GM3 red colour
Working temperature



Travel Condition

Suitable






mt / minute max
Fixed installation
-35°C


Monospiral Reel

180
In Operation
-35°C to + 60°C


Cylindrical Reel

180
"* very special semiconducting compound which acts as a screen; the resistance between the ground conductor and semiconductive external layer of phase conductor must be maximum 500 Ohm measured according to VDE 0472 part 512
electrical Cables.pdf
Electrical Cables- Medium Voltage Power Cable