POWER CABLES

Power Cable

Technical data
H/05 & H/07

  • Minimum bending radius 15 x cable diameter 
  • Temperature range -30°C to +80°C & -30°C to +80°C
  • Working voltage 300/500V & 450/750V
  • Test voltage 2000V 
  • Insulation resistance 1 Mega-ohms x km 
  • Conductor stranding Fine wire to VDE 0295 class 5 
  • Colour coding To VDE 0293 
  • Earth conductor Green/yellow, long striped 
  • VDE regulation 0282 

Rubber Trailing Cable

 

H/05 - Medium-weight rubber sheathed cable for use on hand tools and lightweight workshop tools with medium stress in dry and damp interiors as well as in open-air and wet industrial environments.

H/07 - Heavy rubber sheathed cable for use on heavy appliances with high-level stress in dry and damp conditions as well as in open-air and wet industrial environments.

 

 

  • Conductor of copper, finely stranded, class 5 according to DIN VDE 0295, tinned up to 6mm²

  • Core insulation of dielectric and thermal high-quality, ozone-resistant ethylene-propylene-rubber
    (EPR) compound type 3GI3 according to DIN VDE 0207 part 20, extruded and coloured up to 5 cores, thereafter black with printed no’s.

  • Inner sheath (only for multi-core cable with cross-sections of 16mm² and higher and for multicore cables with 7 or more cores), extruded, filling the interstices compound GM16 according to DIN VDE 0207, part 21, colour natural.

  • Outer sheath of polychloroprene rubber, oil resistant and flame retardant, compound type 5GM3 according to DIN VDE 0207 part 21.

Ruber Trailing Cable Specifications

All dimensions are in mm unless otherwise stated.  Alterations are reserved without notice.

H/05 to VDE 0282 300/500V

Outer Diamiter

Weight Approx Kg/1000m

Amps Per Core

Gland

CAT NO

Section mm2

25°C

30°C

3 x 0,75

7.3

75

14.7

14

 

PG9

 

H/05 3 0.75

3 x 1,0

7.8

87

17.85

17

 

PG9

 

H/05 3 1.0

3 x 1,5

9.5

135

22.05

21

 

PG9

 

H/05 3 1.5

4 x 1,5

9.9

165

22.05

21

 

PG9

 

H/05 4 1.5

4 x 2,5

12.4

235

31.5

30

 

PG11

 

H/05 4 2.5

       

H/07 to VDE 0282 450/750V

Outer Diamiter

Weight Approx Kg/1000m

Amps Per Core

Gland

CAT NO

Section mm2

25°C

30°C

       

1 x 35

16

520

170

162

 

PG21

 

H/07 1 35.0

1 x 50

18

720

212

202

 

PG21

 

H/07 1 50.0

1 x 70

21

940

262

250

 

PG29

 

H/07 1 70.0

1 x 95

23

1220

316

301

 

PG29

 

H/07 1 95.0

1 x 120

25

1510

370

353

 

PG29

 

H/07 1 120.0

1 x 150

28

1850

410

391

 

PG29

 

H/07 1 150.0

3 x 2,5

13

235

31.5

30

 

PG16

 

H/07 3 2.5

3 x 4

15

310

43

41

 

PG16

 

H/07 3 4.0

3 x 6

17

400

55

53

 

PG21

 

H/07 3 6.0

3 x 10

22

810

77

74

 

PG29

 

H/07 3 10.0

3 x 16

25

1000

104

99

 

PG29

 

H/07 3 16.0

3 x 25

30

1470

137

131

 

PG36

 

H/07 3 25.0

3 x 35

34

1950

170

162

 

PG42

 

H/07 3 35.0

4 x 2,5

14

280

31.5

30

 

PG16

 

H/07 4 2.5

4 x 4

17

380

43

41

 

PG21

 

H/07 4 4.0

4 x 6

19

510

55

53

 

PG21

 

H/07 4 6.0

4 x 10

24

940

77

74

 

PG29

 

H/07 4 10.0

4 x 16

27

1250

104

99

 

PG29

 

H/07 4 16.0

4 x 25

32

1850

137

131

 

PG36

 

H/07 4 25.0

4 x 35

36

2310

170

162

 

PG42

 

H/07 4 35.0

4 x 50

41

3160

212

202

 

PG48

 

H/07 4 50.0

4 x 70

46

4250

262

250

 

PG48

 

H/07 4 70.0

5 x 2.5

15

340

23.6

22.5

 

PG16

 

H/07 5 2.5

5 x 4

18

470

33.3

30.75

 

PG21

 

H/07 5 4.0

7 x 1.5

17

316

14.3

13.65

 

PG16

 

H/07 7 1.5

7 x 2.5

20

464

20.5

19.5

 

PG29

 

H/07 7 2.5

7 x 4

23

680

27.98

26.65

 

PG36

 

H/07 7 4.0

7 x 6

26

808

36.17

34.45

 

PG36

 

H/07 7 6.0

8 x 1.5

16

350

12.13

11.55

 

PG29

 

H/07 8 1.5

8 x 2.5

19.2

510

20.5

19.5

 

PG29

 

H/07 8 2.5

12 x 1.5

22

600

12.13

11.55

 

PG29

 

H/07 12 1.5

12 x 2.5

24

745

17.37

16.55

 

PG29

 

H/07 12 2.5

19 x 2.5

30

1250

14.18

13.5

 

PG36

 

H/07 19 2.5

24 x 1.5

28

980

8.82

8.4

 

PG36

 

H/07 24 1.5

24 x 2.5

34

1480

12.6

12

 

PG42

 

H/07 24 2.5